GE Measurement & Control SolutionsGE Measurement & Control Solutions

Home » CO2 » Wall Mount » Telaire 8012 Series
E-mail Print

Telaire 8012 series CO2 switch

Telaire 8012 series CO2 switch

The Telaire 8012 series CO2 switch is a low-cost wall mounted sensing solution for ventilation control. The 8012 provides an intuitive VLI (Visual Level Indicator) display for CO2 thresholds, to maintain air quality in enclosed spaces (school classrooms, offices, gymnasiums, theatres, etc.).

 

Not Available In North America

 

The simple LED array indicates increased CO2 concentrations based on predetermined thresholds. The LED smoothly transitions between blue, green, yellow and red as the CO2 concentration increases.

 

Unlike scientific displays, training to understand PPM values is not prerequisite with this innovative product. Indication shows under ventilation (red) or over ventilation (blue), which translates to low air quality (red) or too much energy being used to heat or cool unnecessary outside air (blue). In a heating only application the blue should be ignored if windows are opened to provide cooling.

Features

  • Reliable (15 years of low-cost infrared sensor manufacturing)
  • Intuitive Light display (VLI)
  • 115/230 Vac power supply
  • 230 V 8A rated output relay
  • Pre-calibrated
  • Maintenance free (calibration maintained with patented ABC Logic)
  • User selectable output switch point
  • RoHS and WEEE compliant

Specifications

Sampling Method Non-dispersive infrared (NDIR), gold plated optics, (with Telaire’s patented ABC Logic self calibration algorithm). Diffusion sampling.
Measurement Range 600-2,000 ppm factory calibrated.
Temperature Dependence 0.2% FS per °C
Stability <2% of FS over life of sensor (15 year typical)
Non Linearity <1% of FS
Pressure Dependence 0.135 of reading per mm Hg
Calibration Interval Not required
Response Time <2 minutes for 90% step change typical
Signal Update Every 4 seconds
Warm Up Time <2 minutes (operational)
10 minutes (maximum accuracy)
Operating Conditions 32°F to 122°F (0°C to 50°C)
0 to 95% RH, non condensing
Storage Conditions -40°F to 158°F (-40°C to 70°C)
Output SPDT Switch 230 V 8A resistive
Display Colored LEDs <600 1st Single Blue
<800 2nd Single Blue
<1000 Green
<1500 Yellow
<2000 Single Red
>2000 Double Red
Connections Screw terminals for 18 to 28 AWG.

Line Input
Neutral Output
Output Switch Common
Output Switch High Value (ON)
Output Switch Low Value (OFF)
Output Switch Levels User selectable at 1000 ppm (default) or 1500 ppm with hysterisis of 300ppm
Auto-On-Off Manual Switch Auto - Relay operated by CO2, LEDs indicate CO2 concentration

On - Relay is in the powered “on” state, all LEDs lit continuously

Off -Relay is in the powered “off” state, all LEDs are off
Anti-recycle Time Minimum ON or OFF period: 10 minutes (in Auto)
Power Supply Requirements 85 VAC to 265 VAC
Power Consumption <1.5 W average
Dimensions 100 mm x 80 mm x 28 mm (h x w x d)
Agency/Certifications CE, WEEE
Warranty Term 18 months

 