T5000 Airestat CO2 & Temperature Transmitter

T5000 Airestat CO2 & Temperature Transmitter

The Telaire® T5000 series Airestat™ CO2 and temperature transmitter is a low-cost wall-mounted sensing solution for demand-controlled ventilation.

The Airestat provides an intuitive VLI (Visual Limit Indicator) display for CO2 thresholds, a passive temperature output (20k thermistor), and a standard analog 0 to 10 volt signal to maintain air quality in enclosed spaces (such as school classrooms, offices, gymnasiums and theaters).

Contact Sales

 

 

 

 

 

Features

  • Low-cost
  • Reliable (15 years of low-cost infrared sensor manufacturing)
  • Pre-calibrated
  • Maintenance free (calibration maintained with patented ABC Logic)
  • Flexible configurations (see matrix, page 2)
  • Intuitive VLI display
  • Two available outputs: analog 0 to 10V and passive temperature (20K thermistor)
  • User-definable thresholds
  • RoHS and WEEE compliant
  • Lifetime calibration warranty

Applications

The Telaire T5000 Series Airestat CO2 and temperature transmitter is a low-cost wall-mounted sensing solution for demand-controlled ventilation.

The Airestat provides an intuitive VLI (Visual Limit Indicator) display for CO2 thresholds, a passive temperature output (20kΩ thermistor), and a standard analog 0 to 10 volt signal to maintain air quality in enclosed spaces (such as school classrooms, offices, gymnasiums and theaters).

Specifications

Sampling Method

Non-dispersive infrared (NDIR), gold plated optics, (with Telaire’s patented ABC Logic self calibration algorithm). Diffusion sampling.

Measurement Range

0 to 2,000 ppm factory calibrated.

Accuracy

± 75 ppm @ 72°F (22°C) when compared with a factory reference or 10% of reading, whichever is greater*

Temperature Dependence

0.2% FS per °F (°C)

Stability

<2% of FS over life of sensor (15 years typical)

Non-Linearity

<1% of FS

Pressure Dependence

0.13% of reading per mm Hg

Calibration Interval

Not required*

Response Time

3 to 5 minutes for 90% step change.

Warm up Time

• <2 minutes (operational)

• 10 minutes (maximum accuracy)

Operating Conditions

• 32°F to 122°F (0°C to 50°C)

• 0 to 95% RH, non condensing

Storage Conditions

• -4°F to 158°F (-20°C to 70°C)

• 0 to 95% RH, non condensing

Temperature

NTC 20k thermistor

Output

• Analog: 0 to 10V (100 Ω output impedance)

Connections

Screw terminals for 18 to 28 AWG

Power Supply Requirements

18 to 30 VAC RMS, 50/60Hz or 18 to 42 VDC, polarity

protected

Power Consumption

1.75 VA average, 2.75 VA peak

Agency/Certifications

FCC Part 15 Class B, CE, RoHS, WEEE

Warranty Term

18 months

* Note: Automatic Background Calibration, or ABC Logic, is a patented self-calibration technique designed to be utilized in applications where concentrations will drop to outside ambient conditions (approximately 400 ppm) at least four times in a 14-day period, typically during unoccupied periods. Full accuracy is achieved after two weeks of operation.